Fluke 2052 Advanced Wire Tracer Product Resources
This article is to provide easy access to online resources for the Fluke 2052 Advanced Wire Tracer. You will find links to useful resources for the 2052 Advanced Wire Tracer below.
Introduction
The 2052 Advanced Wire Tracer is intended for use in locating energized and de-energized wires quickly in walls, ceilings and floors, finding breaks and opens in wiring, and locating breakers and fuses easily.
Quick Reference Guide
Users Manual
Additional Useful Documentation
How To Trace Electrical Wires In Walls
Useful Videos
Fluke 2052 and 2062 Advanced Wire Tracers.
How to trace wire in walls with the Fluke 2052 and 2062 Advanced Wire Tracer.
How to ground the Fluke 2062 and 2052 Advanced Wire Tracer.
Specifications
Specifications: Fluke 2052 Advanced Wire Tracer Kit
General | 2052R Receiver | 2000T Transmitter | i400 AC Current Clamp |
Measurement category | CAT IV 600 V | CAT IV 600 V | CAT IV 600 V, CAT III 1000 V |
Operating voltage | 600 V AC/DC | 600 V AC/DC | 1000 V AC |
Operating frequency | Energized: 6.25 kHz De-Energized: 32.768 kHz | Energized/Loop: 6.25 kHz De-Energized: 32.768 kHz | N/A |
Signal indications | Numeric, bar graph display and audible beep | LEDs and audible beep | N/A |
Response time | Tip Sensor (Energized/De-Energized): 500 ms NCV: 500 ms Battery monitoring: 5 s | Line voltage monitoring: 1 s Battery voltage monitoring: 5 s | N/A |
Current output of signal (typical) | N/A | Energized circuit: High mode: 60 mA rms Low mode: 30 mA rms De-energized circuit: High mode: 110 mA rms Low mode: 40 mA rms Loop mode with test leads: 160 mA rms Loop mode with i400 AC Current Clamp: 385 mA rms | N/A |
Signal voltage output (nominal) | N/A | Energized circuit: High mode: 14 W @ 230 V ac/50 Hz, 3.33 kΩ @ 230 V ac Low mode: 4.6 W @ 230 V ac/50 Hz, 11.5 kΩ @ 230 V ac De-energized circuit: High mode: 31 V RMS, 140 Vp-p, 0.86 W @ 1 kΩ load Low mode: 27.5 V RMS, 120 Vp-p, 0.1 W @ 1 kΩ load Loop mode with test leads: 32 V RMS, 140 Vp-p, 0.87 W @ 1 kΩ load Loop mode with i400 AC Current Clamp: 31 mV, 0.89 W @ 1 Ω load | N/A |
Range detection (open air) | Tip Sensor: Energized Max distance via air: up to 6.1 m (20 ft) Pinpointing: approx. 5 cm (1.97 in) Tip Sensor: De-Energized Max distance via air: up to 4.5 m (14.7 ft) Pinpointing: approx. 5 cm (1.97 in) NCV (40 Hz to 400 Hz) Max. sensitivity: 90 V up to 2 m Min. sensitivity: 600 V up to 1 cm | N/A | |
Current range | N/A | N/A | 400 A |
Basic accuracy | N/A | N/A | 2 % + 0.06 A (45 Hz to 400 Hz) |
Display | |||
Display size | LCD 63 mm (2.5 in) | LEDs | N/A |
Display dimensions (W x H) | 37 mm x 49 mm (1.45 x 1.93 in) | N/A | N/A |
Display Resolution | 240 px x 320 px | N/A | N/A |
Display type | TFT LCD | LEDs | N/A |
Display color | 16-bit | Operating mode LEDs: red Battery status LEDs: green, yellow, red | N/A |
Backlight | Yes | N/A | N/A |
Environmental | |||
Operating temperature | -20 °C to 50 °C (-4 °F to 122 °F) | -20 °C to 50 °C (-4 °F to 122 °F) | -20 °C to 50 °C (-4 °F to 122 °F) |
Operating humidity | 45%: -20 °C to <10 °C or 40 °C to 50 °C (-4 °F to <50 °F or 104 °F to 122 °F) 95% (non-condensing): 10 °C to <30 °C (50 °F to 86 °F) 75%: 30 °C to <40 °C (86 °F to <104 °F) | 45%: -20 °C to <10 °C or 40 °C to 50 °C (-4 °F to <50 °F or 104 °F to 122 °F) 95% (non-condensing): 10 °C to <30 °C (50 °F to 86 °F) 75%: 30 °C to <40 °C (86 °F to <104 °F) | 10 °C to <30 °C (95 %: 50 °F to <86 °F) 30 °C to <40 °C (75 %: 86 °F to <104 °F) 40 °C to <50 °C (45 %: 104 °F to <122 °F) |
Operating altitude | 2000 m (6561 ft) | 2000 m (6561 ft) | 2000 m (6561 ft) |
Transient protection | N/A | N/A | |
Pollution degree | 2 | 2 | 2 |
IP rating | IP 40 | IP 40 | IP 40 |
Drop test | 1 m (3.28 ft) | 1 m (3.28 ft) | 1 m (3.28 ft) |
Mechanical | |||
Power supply | 4 x AA (alkaline) | 8 x AA (alkaline) | N/A |
Power consumption (typical) | 110 mA | High/low mode: 70 mA Loop mode with Clamp: 90 mA Consumption without signal transmission: 10 mA | N/A |
Battery life | Approx. 16 h | High/low mode: approx. 25 h Loop mode: approx. 18 h | N/A |
Low battery indication | Yes | Yes | N/A |
Fuse | N/A | 1.6 A, 700 V, fast-acting, Ø 6 x 32 mm, 50 kA interrupt | N/A |
Maximum conductor size | N/A | N/A | 32 mm (1.26 in) |
Dimensions (L x W x H) | Approx. 183 x 75 x 43 mm (7.2 x 2.95 x 1.69 in) | Approx. 183 x 93 x 50 mm (7.2 x 3.66 x 1.97 in) | Approx. 150 x 70 x 30 mm (5.9 x 2.75 x 1.18 in) |
Weight | Approx. 0.27 kg (0.6 lb) | Approx. 0.57 kg (1.25 lb) | Approx. 0.114 kg (0.25 lb) |
Mechanical | 2000ACC Test Lead Accessory Kit |
Includes | 2x 1 m test leads (red, black), 1x 7 m test lead (green), 2x test probes (black), 2x alligator clips (red, black), 2x outlet blade adapters (red, black), 2x outlet round adapters (red, black) |
Measurement category | CAT IV 600 V (test leads), CAT II 1000 V (test probes), CAT IV 600 V (alligator clips), CAT II 300 V (outlet adapters) |
Operating voltage and current | 600 V, 10 A max. (red/black leads), 600 V, 10 A max. (green lead), 1000 V, 8 A max. (black probe) 600 V, 10 A max. (alligator clips), 300 V, 10 A max. (outlet adapters) |
Operating temperature | 0 °C to 50 °C (32 °F to 122 °F) |
Operating humidity | 10 °C to <30 °C (95 %: 50 °F to <86 °F), 30 °C to <40 °C (75 %: 86 °F to <104 °F), 40 °C to <50 °C (45 %: 104 °F to <122 °F) |
Storage temperature and humidity | 0 °C to 60 °C (32 °F to 140 °F), |
Operating altitude | 2000 m (6561 ft) |
Pollution degree | 2 |
Water and dust resistance | IP 20 |
Drop proof | 1 m (3.28 ft) |
Dimensions | Red/black leads: 1 m (3.28 ft), Green lead: 7 m (22.97 ft), Alligator clips: approx. 95 x 45 x 24 mm (3.74 x 1.77 x 0.94 in), Outlet adapters: 72 x 18 x 18 mm (2.83 x 0.71 x 0.71 in) |
Weight | Approx. 0.4 kg (0.88 lb) |