This Article is about walking through the process of using (3) AC current probes and (1) DC current probe.

Below are some screen shots of the Fluke-1775, the first screen shot is reviewing the Information menu and details about the current probe sensors connected to the meter. The A, B and C phases are showing the 1500A AC Flexi current probes and the Neutral channel is connected to one of the AC/DC current probes in this case model number 80i-110s.The model number of the adapter cable required when using the 80i-110s is 17XX-Clamp-1V and the ratio needs to be change in the Fluke-1775 from 1:1 to 0.1:1. 

  

 

Here is the Information menu reviewing the sensors and they are the (3) 1500A Flexi current probe and the 80i-110s current probe labeled Adapter 1mV/A 1V which is the labeling of the clamp adapter cable. 

You need to exit out of the Information menu and go into the PQ Logger setup and select Measurement settings and make adjustments for the Neutral channel for the 80i-110s current probe from 1:1 to 0.1:1. 

The next step is going to the PQ Logger mode and select Verify Connections and then select Verify Meter and it will show the voltage and current measurements. Below is an example of the screen, notice the scale does not reflect AC or DC just V and A and that is normal, the meter in the example is not connected to a circuit otherwise you would see larger values. 

Below is a table listing the different current probes and the two adapters available you will need to order depending on what current probe you select.